CHINT 169237 ā NM8L 125A 3P RCCB
125A rated, 3-pole residual current MCCB with 50kA breaking capacity and 100% Ics. Built on NM8L-250 frame, with X1-type earth leakage protection (0.05 / 0.1 / 0.2 / 0.5A), adjustable thermal magnetic trip unit, and T1 configurable break time.
š¹ Description (English):
The CHINT 169237 ā NM8L-250S/125/3 X1 T1 is a high-performance molded case circuit breaker with integrated residual current protection, designed for 125A circuits in industrial environments. Built on the NM8L-250 frame, it provides enhanced durability, thermal stability, and mechanical strength. Featuring a 50kA interrupting capacity and 100% Ics, it offers robust protection against overloads, short circuits, and earth faults. X1-type leakage protection and adjustable thermal magnetic tripping make it suitable for sensitive equipment. T1 delay settings allow tailored fault response.
š¹ Key Features:
⢠Rated current: 125A
⢠Breaking capacity: 50kA (Icu), 100% Ics
⢠Residual current protection: X1 (0.05 / 0.1 / 0.2 / 0.5A)
⢠Adjustable thermal magnetic trip unit
⢠Configurable delay settings: T1 (0.1 / 0.3 / 0.5 / 1s)
⢠Frame: NM8L-250 (heavy-duty)
⢠Conforms to IEC 60947-2
⢠Certified: CCC, CE, KEMA
⢠DIN rail or panel mounting
š¹ Technical Specifications (English):
Parameter Value
Model NM8L-250S/125/3 X1 T1
Part Number CHINT 169237
Rated Current 125A
Number of Poles 3P
Breaking Capacity Icu: 50kA, Ics: 100%
Residual Protection X1: 0.05 / 0.1 / 0.2 / 0.5 A
Trip Unit Type Thermal-Magnetic (Adjustable)
Break Time Settings T1: 0.1 / 0.3 / 0.5 / 1 s
Frame Size NM8L-250
Mounting DIN rail or panel
Standards IEC 60947-2
Certifications CCC, CE, KEMA